
- During construction: to provide external fresh air required to dilute the pollutants produced by the machines and by blasting used during different construction stages to allow a safe environment for workers working inside the tunnel.
- During normal operation of the tunnel: this factor is dominant for tunnels subject to high traffic load and frequent congested traffic. The normal functioning of the ventilation system should also ensure prevention of dust from outside entering the tunnel.
- During emergencies like fire etc: This factor is usually dominant for non-urban tunnels and highway tunnels.
Types of ventilation systems and factors affecting choice of a ventilation system for a tunnel
As per IRC: 91-2019 – Guidelines for Road Tunnels, RVS 09.02.31, NFPA 502 and PIARC recommendations, there are different types of ventilation systems based on different mechanisms as explained below:
Natural or non-mechanized ventilation system
It can be induced by air temperature and meteorological conditions or by traffic flow. This system involves no installation of fans for mechanical airflow in the traffic zone. In tunnels, there is always some kind of natural ventilation driven by various factors such as atmospheric conditions viz. wind, pressure difference between portals, some chimney or convective effect and traffic. The schematic diagram showing factors affecting natural ventilation inside the tunnel is shown in Figure 1.

Longitudinal ventilation system
This system is generally selected for unidirectional tunnels with length varying from 500 to 4000 m and light traffic density. Among the mechanized ventilation systems, this system is the easiest and cheapest ventilation systems. Longitudinal ventilation is accomplished by using jet fans by accelerating a small pocket of the air present in the tunnel, through an exchange of momentum, are able to induce, on the overall air inside the tunnel, a movement in the desired direction. A schematic diagram of longitudinal ventilation system is shown in Figure 2.



As per RVS 09.02.31, the longitudinal velocity of air inside the tunnel arising due to meteorological conditions and traffic flow should not exceed 10 m/s. Also, to raise the operational safety under the fire effects and minimize turbulence, the fans and ventilators shall be deployed over the length of the tunnel.
Semi-Transverse ventilation system
In this system, the air supply is introduced via the tunnel portals while the exhaust air is extracted over the length through equally spaced smoke extraction dampers throughout the tunnel. The extracted air flows via overhead duct outside the tunnel. In the reversible semi-transverse ventilation system, fresh air is introduced via ducts and the exhaust air flows longitudinally to the two portals.
This system uses a combination of jet fans and axial flow fans. The maximum longitudinal velocity of air flow should be 10m/s as per RVS 09.02.31. The smoke-extraction dampers shall be opened fully in the area of the scene of fire and other dampers shall be closed. The schematic diagram showing semi-transverse ventilation system is shown in Figure 3.
Fully transverse ventilation system
With fully-transverse ventilation system, supply air is introduced, distributed all over the length of the tunnel, and exhaust air is extracted. The air streams (injected fresh air and extracted exhaust air) create a flow in the main tube, in transverse direction to the longitudinal axis of the tunnel. Longitudinal air flow in the tunnel is difficult to control, hence, the independent ventilation sections are created in which fresh air injection and exhaust air extraction can be operated separately. A butterfly flap is installed between two ventilation sections to separate them.
In the emergency mode, the smoke extraction dampers in the fire area are opened and the remaining dampers are closed and smoke is evacuated through the ceiling which is the reason that this ventilation system is suitable in very long tunnels. The schematic diagram of fully transverse ventilation system during normal and emergency operation is shown in Figure 4.


Certain factors need to be considered while selecting and designing a particular type of tunnel ventilation system:
- Cost Effectiveness – As regard to the economic considerations, 20 years is anticipated as the service life of electric machine parts and fittings as per RVS 09.02.31.
- Safety Analysis during operation.
- Heat Release Rate (HRR) of fire: It is expressed in megawatts as it is the rate at which energy is released by fire. It depends on types of goods passing through tunnel and flammability. Tunnels in India are generally designed for 50 MW. HRR ratings for tunnels as per different specifications is mentioned in Table 1.
- Traffic data: Unidirectional traffic, bidirectional traffic, maximum traffic flow, Passenger Car Unit (PCU), no. of petrol/diesel vehicles, vehicular emissions and admissible contamination (levels for CO, NOx, etc.).
- Geometric Data: Length of tunnel; gradient of tunnel; cross-sectional area of tunnel; altitude of tunnel; meteorological and geographical data such as latitude, air density, relative humidity, wind velocity, etc.
Table 1: HRR rating as per different guidelines | ||||
Fire HRR for Different Guidelines | ||||
Guidelines | NFPA 502 | PIARC | BD 78/79 | IRC SP 91-2019 |
Types of Fire Load | Heat Release Rate (MW) | Heat Release Rate (MW) | Heat Release Rate (MW) | Heat Release Rate (MW) |
Passenger Car | 5-10 | 5-10 | 5 | Types of goods Passing through the tunnel & Potential flammability, this is generally 50MW Minimum. |
Light duty Vehicle | 10-20 | 15 | 15 | |
Coach & Bus | 20-30 | 20 | 20 | |
Lorry & Heavy Good Vehicle | 70-200 | 30-50 | 30-100 |
Fresh air requirement: As per IRC: SP:91-2019, minimum fresh air requirement for normal traffic condition might be small. However, ventilation system shall be designed to accommodate sudden demands for high emitting Heavy Goods Vehicles and in that case, an air-exchange rate of at least 4 times per hour shall be considered.
Carbon Monoxide (CO) concentration: As per RVS 09.02.31, a maximum design limit of 100 ppm for CO concentration shall be considered. However, tunnel shall be immediately barricaded if:
- CO levels ≥ 100 ppm for a period of more than 10 minutes.
- CO levels ≥ 150 ppm.
Particulate Matter (PM) emissions: The presence of PM in the tunnel reduces the visibility inside the tunnel. Visibility is reduced by the scattering and absorption of radiation in the visible wavelength range. The tunnel ventilation system must provide visibility levels that exceed the minimum vehicle stopping distance at the design speed. PIARC recommendations provides design and operation values of extinction coefficient for visibility.
General Technical specifications of different equipment of ventilation system and functional testing procedure during operation
RVS 09.02.31 describes a detailed section on technical specifications that are to be observed in all the components of ventilation system including exhaust fans, jet fans, ventilation ducts and auxiliary equipment. All the equipment (fans, auxiliary equipment and cabling) to operate in flue gas conditions (fire), and they must continue to operate at a temperature of 400˚C over a two-hour period. Jet fans in longitudinal tunnel, shall be spaced at a distance of ≥ 200m, a temperature stability of 250˚C over a 60-minute period.
Jet fans: All jet fans including mountings, and sound absorbers, shall be manufactured from corrosion-resistant material. The jet fans shall be mounted in a way which limits vibrations.

Axial fans: Axial fans comprise of fan with a wheel, guide wheel and electric motor, as well as nozzle, diffuser, shut-off valve. Provisions shall be made to monitor vibrations in the fan motor unit and temperature of coil and bearings. The quantity of air discharged and the change in pressure in the fans must be recorded regularly and proper documentation of reports shall be done. The fans shall be usually located in portal stations or caverns and it should be ensured that proper access is available and its maintenance should not hamper the traffic flow.
Smoke Dampers: These assist in the targeted regulation of the exchange of air between the carriageway and the exhaust air ducts. The dampers shall perform satisfactorily in the transverse ventilated tunnels both during normal operation and in the case of fire. The desired width of the dampers shall be 3 m and the minimum quantity of exhaust air of 120 m³/s flows through the dampers in the event of fire.
Functional testing of ventilation system

Monthly testing: All the equipment including fans, ventilators, dampers shall be inspected monthly as regards to their functionality and under all volume flows and damper positions.
Annual functional testing: This shall be carried out together with the annual visual inspection with the aim of inspecting and reporting this back to the central control system.
Every six years: suction tests involving volume flow measurements shall be performed in order to examine the minimum exhaust air volume flow required at every smoke damper.
Overview of Ventilation System to be adopted in Z-Morh Tunnel Project Brief
Z-Morh Tunnel is located in the UT of J&K. It is a 6.426 km long tunnel with 6.412 km parallel escape tunnel. The West Portal (Srinagar side) is at an elevation of EL 2489 m and East Portal (Sonamarg Side) is at an elevation of EL 2634 m. The slope of the tunnel is rising from Srinagar to Sonamarg side at 2.27%. The maximum overburden for the tunnel is 1075 m. The main tunnel is connected with escape tunnel with motorable cross-passages at every 750 m and pedestrian cross passages at every 250 m. There is a ventilation adit of length 575 m in the middle of the alignment of the tunnel. The general tunnel layout showing main and escape tunnel is as per Figure 8.

Traffic forecast and Fire-design data
The key traffic data is as follows:
- Bidirectional traffic in main tunnel.
- 2 lanes, 1 lane per direction.
- Design speed – 80 kmph.
- Peak hour traffic: 1070 vehicles/hour.
- The percentage of diesel cars in India is highly variable and hence it is assumed that the diesel share in the running fleet is 35%.
- Fire rating: 50 MW.
Based on the selection criteria presented in section 2, a semi-transverse ventilation system will be used in the Z-Morh Tunnel. The advantage of semi-transverse ventilation over fully-transverse ventilation system for long tunnels is the relative simplicity of the system, lower cost and ease of maintenance. The general layout of ventilation system is shown in Figure 9.

The main characteristics of the ventilation system are:
- Normal operation with exhaust extraction though ventilation station at the center of the tunnel. The jet fans installed at the portals equilibrate the flow conditions in case of asymmetric traffic.
- Concentrated smoke extraction at the fire location through the exhaust duct in case of fire.
- Motorized smoke-extraction dampers installed in the false ceiling allow for a precise localization of the smoke-extraction zone. Jet fans control the airflow in the tunnel for achieving an optimum smoke extraction. Smoke is ejected through the ventilation station.
- Smoke discharge through the closed portal in case of fire in the vicinity of a portal, in the section without false ceiling.
- The extraction duct is interrupted in the portal areas. This allows for optimum installation of large jet fans.
- The remaining jet fans are installed in the lay-bys.

The main components of the main tunnel ventilation system are:
- Ventilation station in the middle of the tunnel with 3 large-diameter exhaust fans.
- Exhaust duct in the upper part of the tunnel cross section, interrupted at the portals for allowing the installation of jet fans.
- Remotely controlled motorized dampers for exhaust and smoke extraction in the exhaust duct, installed at regular distances of about 100 m (shorter distances apply at the ends and centre of the exhaust tunnels, where dampers are located with a distance of about 25 m).
- Remotely controlled vertically mounted motorized dampers in the exhaust duct, separating the West and the East side from the smoke-extraction station.
- Jet fans distributed along the tunnel length.
- Ventilation sensors (pollution sensors and anemometers).
Tunnel Ventilation System plays an integral role in the stability and functionality of tunnels after construction. The ventilation system should be designed with due diligence and taking proper care of all the parameters and standard international codes mentioned above. Any compromise in the ventilation system may result in hazardous situation inside the tunnel. There have been instances where due to failure of ventilation system and fire-fighting system, a huge catastrophic damage has occurred. Salang tunnel accident in Afghanistan is one such example.
As mentioned earlier, India does not have any specific regulation for tunnel ventilation system, hence, experiences from different road tunnels shall be compiled and shared at appropriate platform for future reference and an eternal guidebook. This will increase the expertise of Indian professionals in this field and reduce the reliance on foreign expertise while designing ventilation system for Indian tunnels.
The tunnel ventilation system should be maintained adhering to all the standard technical specifications. To avoid any negligence by the Operation & Maintenance (O&M) Contractor during operation of the tunnel pertaining to the safety of the ventilation system and E&M installations, contractual provisions shall be included for penalizing the Contractor for such practices.
References
- IRC: SP: 91-2019 – Guidelines for Road Tunnels.
- Austrian standard RVS 09.02.31, “Tunnel equipment – ventilation – basic principles”, 1st of august, 2008.
- Standard NFPA 502, USA, “Standard for road tunnels, bridges and other limited access highways”, 2011 Edition.
- PIARC Committee on Road Tunnels Operation (C3.3): Systems and equipment for fire and smoke control in road tunnels (2007).
- PIARC Technical Committee on Road Tunnel Operation (C5): Road Tunnels: Vehicle Emissions and air demand for ventilation (2004).